Damper Details and Duct Connections

Summary

This chapter adds detail to dampers and duct connections. It covers ceiling and wall gravity dampers, flat and airfoil blades, blade flutter, damper actuators and throttling, blast gates and slide gate dampers, and lab exhaust isolation and bypass dampers. It also covers nested inlet vanes and pre-spin, inlet venturis, free-standing and bolt-on inlet boxes and inlet box horns, flexible connectors, tube adapters, bolted flange and slip connections, and the ASA pipe flange bolt pattern. After completing it, readers can specify how a fan connects to its ductwork and controls.

Concepts Covered

This chapter covers the following 22 concepts from the learning graph:

Concept Concept Impact Score
Ceiling Type Gravity Damper 1
Wall Type Gravity Damper 1
Blade Flutter 4
Flat Blade Damper 2
Inlet Venturi 1
Free-Standing Inlet Box 4
Flexible Connector 4
Nested Inlet Vanes 1
Damper Actuator 3
Airfoil Blade Damper 1
Inlet Box Horn 1
Bolt-On Inlet Box 2
Tube Adapter and Sleeve 1
Blast Gate 3
Damper Throttling 1
Lab Exhaust Isolation Damper 1
Lab Exhaust Bypass Damper 1
Bolted Flange Connection 1
Slip Connection 2
Slide Gate Damper 1
ASA Pipe Flange Bolt Pattern 1
Pre-Spin 1

Prerequisites

This chapter builds on concepts from:

Where the Fan Meets the Building

Breeze waving welcome A fan rarely fails on paper. It fails at the damper that flutters, the inlet box that will not line up, or the rigid joint that carries vibration into the ductwork. This chapter gives you the details that decide whether an order installs cleanly. Let's follow the airflow.

Chapter 18 introduced dampers, inlet vanes, inlet boxes and companion flanges as categories. This chapter goes one level deeper, to the details that appear on an order or a submittal drawing: the type of gravity damper, the blade profile, the actuator, the particular throttling device a pressure blower takes, the inlet box style, and how the fan physically joins the ductwork. The FanPedia accessory pages (pp. 125–145) and technical descriptions (pp. 180–194) are the sources for the product statements below.

Gravity Dampers: Ceiling and Wall Types

A gravity damper opens when airflow pushes on its blades and closes under its own weight when the fan stops. It needs no power and no controls, which makes it the default backdraft device on small commercial exhaust fans. FanPedia (p. 136) shows three commercial-grade gravity dampers: the butterfly type built into roof-mounted upblast fans, covered in Chapter 18, and two more that matter here.

A ceiling type gravity damper is a parallel blade, end-pivoted damper that opens automatically when the fan is energized and closes by gravity when power is turned off (FanPedia p. 181). Its job is to stop air from flowing backward through the system while also keeping out rain and snow. As the name says, it goes with fans and openings in a ceiling, where the damper sits in a horizontal plane.

A wall type gravity damper has the same technical description, word for word: parallel blades, end pivots, opening on fan start, closing by gravity at fan stop, blocking backflow and weather (p. 181). The difference is the mounting plane. A wall type damper serves a fan or opening in a vertical wall, so its blades hang closed rather than lying closed. When you quote either one, confirm the mounting orientation with the customer, because the two are not interchangeable in the field.

The three gravity damper types compare as follows.

Gravity damper Blade style Where it is used What it prevents
Butterfly type Butterfly, integral to the fan Roof-mounted upblast fans Backdraft of outside air; weather when the fan is off
Ceiling type Parallel blade, end-pivoted Ceiling openings (horizontal plane) Backflow through the system; rain and snow
Wall type Parallel blade, end-pivoted Wall openings (vertical plane) Backflow through the system; rain and snow

Damper Blades: Flat or Airfoil, and the Flutter Problem

Industrial outlet dampers come in two blade types (FanPedia p. 137). A flat blade damper (Type 1) uses plain flat blades. FanPedia shows it on both parallel and opposed blade outlet dampers, but it does not say when to choose flat blades over airfoil blades, so ask the application engineer or check the current catalog.

An airfoil blade damper (Type 2) uses blades with a streamlined, wing-like cross section. In general engineering terms, the airfoil shape lowers the pressure drop across the open damper, reduces turbulence and noise, and makes each blade stiffer for its weight. FanPedia shows parallel and opposed blade outlet dampers in both types, but the parallel blade inlet box damper is offered as Type 2 only, so a quote that pairs an inlet box damper with flat blades is a configuration error to catch early.

Blade flutter is a rapid, uneven oscillation of damper blades that are only partly open. It happens when the airflow alone is holding the blades in position. FanPedia's description of motorized dampers (p. 182) names the cause: in low-flow conditions, the velocity pressure of the airstream may only partially open automatic damper blades, and the result is blade flutter and potentially more noise. Flutter also wears pivots and bearings over time.

The cure for flutter is to stop relying on the airstream. A damper actuator is a powered operator, electric or pneumatic, that drives the damper blades to a commanded position instead of letting the air position them. FanPedia shows motorized commercial dampers with an actuator at the center pivot or at the end pivot (p. 136), and industrial outlet dampers with either a manual handle or an actuator (p. 137). Inlet vanes, blast gates and lab exhaust dampers can also be furnished with actuators, which is how any of these devices joins an automatic control loop.

A Low-Flow Gravity Damper Will Chatter

Breeze cautioning A common trap is putting an airflow-opened damper on a fan that will spend long hours at low flow, such as one on a VFD. The blades hover half-open and flutter. If the fan will run well below full flow, quote a motorized damper with an actuator so the blades are driven fully open.

Damper Throttling

Damper throttling is controlling a fan's airflow by partly closing a damper so that it adds resistance to the system. The fan does not change. The system curve does: closing the damper makes the system steeper, so it crosses the fan curve at a lower airflow and a higher pressure. FanPedia describes this for outlet dampers as "shifting the operating point to the left of the rating point," and notes that the horsepower savings depend on the position on the fan curve and are usually much less than with other methods (pp. 182–183). Throttling is still the least expensive control and is a sensible choice when reduced capacity is needed only occasionally, or when the air is hot, humid or dirty.

The system curve itself is the familiar square law from Chapter 10: the pressure needed to push air through a fixed system rises with the square of the airflow. Throttling multiplies the system's resistance coefficient.

\[ P_{sys} = m \, k \, Q^2 \]

where:

  • \( P_{sys} \) is the static pressure the system needs, in in. wg
  • \( Q \) is the airflow, in CFM
  • \( k \) is the resistance coefficient of the system with the damper wide open
  • \( m \) is the resistance multiplier added by the damper (1.0 when wide open, larger as it closes)

The chart below lets you close a damper step by step and watch the operating point move. Its numbers are illustrative, chosen to make the pattern easy to see.

Diagram: Damper Throttling Operating Point Explorer

Run Damper Throttling Operating Point Explorer Fullscreen

Damper Throttling Operating Point Explorer

Type: chart sim-id: ch19-damper-throttling-explorer
Library: Plotly
Status: Specified
Bloom Level: Understand
Bloom Verb: interpret
Learning Objective: The learner will interpret how closing an outlet damper moves a fan's operating point along its fan curve, predicting the direction of change in airflow and static pressure before each new damper setting is revealed.

Prerequisites: fan curve, system curve and operating point (Chapter 10); damper throttling and the resistance multiplier m (defined in the section "Damper Throttling" above).

Evidence of Mastery: Before each of the five closing steps is revealed, the learner commits a prediction for airflow (higher, lower, same) and for static pressure (higher, lower, same). A prediction pair is correct when both directions match the Rules. Mastery is 5 of 5 steps with both directions correct. Viewing the chart after the reveal is exploration, not evidence.

Misconceptions: (1) Closing a damper lowers the pressure the fan produces. (2) Closing a damper changes the fan curve. (3) Airflow falls in proportion to how far the damper is closed.

Instructional Rationale: Interpreting a graphical model requires predicting before seeing, so each step locks a prediction and then shows the new intersection with the numbers. Step-through with visible values, not animation, lets the learner compare consecutive operating points.

Content:

Fan curve (illustrative, labeled "illustrative"): static pressure in in. wg as a function of airflow in CFM.

System curves: six damper settings, each with its resistance multiplier and operating point.

Damper setting label Multiplier m Operating airflow (CFM) Operating static pressure (in. wg)
Wide open 1.0 10,000 5.00
Step 1 1.5 8,402 5.29
Step 2 2.0 7,385 5.45
Step 3 3.0 6,124 5.63
Step 4 4.0 5,345 5.71
Step 5 6.0 4,399 5.81

Labels: axis titles "Airflow (CFM)" and "Static pressure (in. wg)"; curve names "Fan curve" and "System curve, m = "; operating point label "Operating point: CFM at in. wg". Note shown at all times: "Values are illustrative. Real fan curves are read from the catalog."

Provenance: All curves and values are illustrative, computed from the Rules. The qualitative behavior (operating point moves to the left of the rating point; horsepower savings usually much less than other methods) is from FanPedia pp. 182–183 and the chapter section "Damper Throttling".

Rules: Fan curve: P_fan(Q) = 6.0 − (Q / 10,000)² in. wg, plotted for Q from 0 to 16,000 CFM. System curve: P_sys(Q) = 5.0 × m × (Q / 10,000)² in. wg, plotted over the same range. Operating point: (Q / 10,000)² = 6.0 / (1 + 5.0 × m); Q = 10,000 × √(6.0 / (1 + 5.0m)); P = 6.0 − 6.0 / (1 + 5.0m). Airflow is rounded to the nearest 1 CFM and pressure to 0.01 in. wg, with halves rounded up. The multiplier takes only the six values in Content, in the order listed; m never decreases during the challenge. For every step, the correct prediction is airflow lower and static pressure higher.

Learner Activity:

  1. The learner sees the wide-open state and reads its operating point.
  2. The learner presses "Close damper one step". Before the new system curve appears, the learner chooses airflow higher, lower or same, and static pressure higher, lower or same, then presses "Check".
  3. The new system curve and operating point appear, with the previous operating point still marked, and the feedback for that step is shown.
  4. Steps 2 and 3 repeat through Step 5.
  5. After Step 5, a "Reset" control returns to wide open and the learner may step freely without predictions.

Feedback: Five steps, fixed order, one attempt each. Correct: "Correct: closing the damper steepens the system curve, so the fan slides left and up its own curve to CFM at in. wg." Wrong pressure direction: "The fan curve did not move. A steeper system curve meets the same fan curve at lower airflow, where this fan makes more pressure, not less." Wrong airflow direction: "More resistance always means less airflow at the new intersection." After Step 5, a summary shows "Predictions correct: n of 5" and the note "From wide open to Step 5, m rose 6 times but airflow fell by 56%, not by 6 times."

Starting State: Fan curve, wide-open system curve and the operating point at 10,000 CFM and 5.00 in. wg. The prompt reads "If you close the damper one step, where will the fan operate?"

Chapter Anchors: The chapter states that closing the damper moves the operating point to lower airflow and higher pressure, and that the chart's numbers are illustrative. Wide-open operating point 10,000 CFM at 5.00 in. wg.

Blast Gates and Slide Gate Dampers

Pressure blowers and other small high-pressure fans usually discharge into pipe rather than sheet-metal duct, and they have their own throttling devices.

A blast gate is a wafer-type butterfly valve that mounts to the fan's outlet flange and controls flow all the way to full shutoff (FanPedia pp. 125, 180). It is also known as a waffle damper, wafer-type butterfly valve or butterfly damper. It is available for automatic control, has a maximum temperature of 250°F, and its bolt pattern matches a 125# ASA pipe flange, a standard described later in this chapter. On an order, a blast gate answers the question "Can the customer shut this blower off at the outlet without a separate valve?"

A slide gate damper is a flat gate that slides across the airway in a frame to throttle flow manually. Twin City Fan offers it for cast aluminum pressure blowers, with a cast aluminum frame and a galvanized steel gate, on the inlet or the outlet (FanPedia pp. 127, 192). It is a set-and-leave adjustment, typically used to trim a blower to its system during startup.

Lab Exhaust Isolation and Bypass Dampers

Laboratory exhaust fans dilute fume-hood exhaust with outside air drawn through a bypass air plenum and through the fan's nozzle or windband, then throw the mixture high above the roof (FanPedia pp. 4, 6). FanPedia's lab exhaust damper page (p. 138) shows three items on these fans: isolation dampers, bypass dampers and actuators, on models BCIFE and BAIFE and on models TVIFE, QIFE, QFE and TFE. FanPedia names the parts without describing their duty, so the descriptions below follow standard lab exhaust practice.

A lab exhaust isolation damper sits between the exhaust plenum and an individual fan. It closes when that fan is off, so that a running fan on the same plenum cannot pull air backward through the idle one and so that the idle fan can be serviced. Lab systems often run several fans on one plenum with one on standby, which is why the isolation damper is standard on many of these layouts.

A lab exhaust bypass damper controls the outside air admitted through the bypass air plenum. As fume hood sashes close and the building's exhaust demand drops, the bypass damper opens to make up the difference, so the fan keeps moving a nearly constant volume and holds the discharge velocity that carries the plume clear of the building. Both dampers are normally fitted with actuators tied to the building control system.

Two Dampers, Two Different Jobs

Breeze thinking Notice that the bypass damper exists to keep fan airflow constant while the building's demand changes, while the isolation damper exists to make a stopped fan look like a closed wall. One manages flow; the other manages direction.

Nested Inlet Vanes and Pre-Spin

Inlet vanes control flow by changing how air enters the impeller rather than by adding resistance downstream. Pre-spin is the swirl that inlet vanes or an inlet box damper give the incoming air, turning it in the same direction the impeller rotates (FanPedia pp. 139, 183, 188). Because the air already has some of the rotation the impeller would otherwise have to give it, the impeller does less work on each pound of air. That is why FanPedia credits the inlet box damper with "a savings in horsepower at reduced loads," and why pre-spin control usually saves more power than outlet damper throttling.

The general engineering basis is Euler's turbomachinery equation, which gives the work an impeller does on each unit mass of air:

\[ w = U_2 \, V_{\theta 2} - U_1 \, V_{\theta 1} \]

where:

  • \( w \) is the work done per unit mass of air
  • \( U_1 \) and \( U_2 \) are the blade speeds at the impeller inlet and outlet
  • \( V_{\theta 1} \) and \( V_{\theta 2} \) are the tangential (swirl) components of air velocity at the inlet and outlet

With no pre-spin, \( V_{\theta 1} \) is zero. Pre-spin in the direction of rotation makes \( V_{\theta 1} \) positive, so the second term reduces \( w \): the fan develops less pressure and moves less air, and it draws less power doing so.

Nested inlet vanes do the same job as the external inlet vanes of Chapter 18, but the vanes are built into the inlet funnel instead of a separate housing bolted to the inlet (FanPedia pp. 139, 188). They are applied to clean airstreams up to 600°F; external vanes are the choice for contaminated airstreams. Both come standard with a manual handle and can take an actuator. The trade-off is serviceability: replacing nested vanes requires replacing the inlet funnel assembly.

Diagram: External and Nested Inlet Vanes

Run External and Nested Inlet Vanes Fullscreen

External and Nested Inlet Vanes

sim-id: ch19-inlet-vanes-overlay
Library: html + FP.Overlay
Status: built
Bloom Level: Remember
Learning Objective: The learner will identify the external inlet vanes, nested inlet vanes, inlet funnel, manual handle, impeller and the pre-spin arrows on FanPedia's inlet vane drawings, given each part's job or look.

Content: 6 numbered markers: Manual handle, External inlet vanes, Impeller, Pre-spin, Nested inlet vanes, Inlet funnel

Provenance: FanPedia page 139, "Inlet Vanes: Industrial Grade, external inlet vane (top) and nested inlet vane (bottom), each with its close-up photo", with the printed labels removed. Drawing: FanPedia, Twin City Fan, p. 139.

The table below compares the two vane styles on the points an order turns on.

Point of comparison External inlet vanes Nested inlet vanes
Location Own housing, bolted to the fan inlet Within the inlet funnel
Airstream Contaminated, or high temperature up to 600°F Clean, up to 600°F
Operator Manual handle standard, actuator optional Manual handle standard, actuator optional
Vane replacement Vane assembly Entire inlet funnel assembly

The sorter below asks you to match field situations to the damper or vane that fits them.

Diagram: Flow Control Device Sorter

Run Flow Control Device Sorter Fullscreen

Flow Control Device Sorter

Type: microsim sim-id: ch19-flow-control-device-sorter
Library: p5.js
Status: Specified
Bloom Level: Understand
Bloom Verb: classify
Learning Objective: The learner will classify eight field situations by the damper or vane device that fits each one, with at least 7 of 8 correct on the first attempt.

Prerequisites: ceiling type and wall type gravity dampers, blast gate, slide gate damper, nested inlet vanes, pre-spin, lab exhaust isolation and bypass dampers (all defined in the sections above).

Evidence of Mastery: The learner assigns each of the 8 situation cards to one of the 7 device bins. An assignment is correct when it matches the Correct device column. Mastery is 7 of 8 correct on the first attempt.

Misconceptions: (1) Ceiling and wall gravity dampers are interchangeable. (2) A slide gate is the shutoff device for any pressure blower. (3) Nested and external inlet vanes suit the same airstreams. (4) Isolation and bypass dampers on a lab fan do the same job.

Instructional Rationale: Classifying realistic order situations makes the learner use the defining feature of each device rather than recall its name. Immediate, reason-based feedback after each card corrects a confusion before the next card.

Content:

Device bins (7): Ceiling type gravity damper; Wall type gravity damper; Blast gate; Slide gate damper; Nested inlet vanes; Lab exhaust isolation damper; Lab exhaust bypass damper.

# Situation card shown to the learner Correct device Why (shown as feedback)
1 A fan exhausts through a horizontal opening in a ceiling. When it stops, nothing powered may close the opening, but backflow and rain must be kept out. Ceiling type gravity damper It opens on fan start and closes by gravity, and it is the type for a ceiling opening.
2 A fan exhausts through a vertical wall. When it stops, the opening must close by itself against backdraft, rain and snow. Wall type gravity damper Same gravity action as the ceiling type, but built for the vertical plane of a wall.
3 A pressure blower's outlet must be able to shut off flow completely, and the outlet bolts to a 125# ASA pipe flange. The airstream is 200°F. Blast gate A blast gate is a wafer butterfly valve at the outlet flange that controls flow to full shutoff, rated to 250°F, with a 125# ASA bolt pattern.
4 The same kind of blower outlet needs shutoff, and the plant wants an actuator to open and close it automatically. Blast gate Blast gates are available for automatic control; a slide gate damper is manual.
5 A cast aluminum pressure blower needs a simple manual adjustment at its inlet that a technician sets once at startup. Slide gate damper Slide gate dampers fit cast aluminum pressure blowers, mount on the inlet or outlet, and give manual adjustment.
6 A clean 400°F airstream needs flow control with horsepower savings, and the vanes should sit inside the inlet funnel rather than in a separate bolted housing. Nested inlet vanes Nested vanes pre-spin the air from within the inlet funnel and suit clean air up to 600°F.
7 Three lab exhaust fans share one plenum, with one on standby. The standby fan must not let air run backward through it. Lab exhaust isolation damper The isolation damper closes behind an idle fan so the running fans cannot draw air back through it.
8 As fume hood sashes close, building exhaust drops, but the lab fan must keep its airflow and plume height constant. Lab exhaust bypass damper The bypass damper opens to admit outside air through the bypass plenum and make up the lost flow.

Provenance: Device facts from FanPedia pp. 125, 127, 136, 138, 139, 180, 181, 188 and 192 and the chapter sections above. The duties of lab exhaust isolation and bypass dampers follow standard lab exhaust practice, as the chapter states. Situation cards are illustrative scenarios.

Rules: Each card has exactly one correct bin. A card is scored on the first bin it is placed in; later moves do not change the score. Blast gate is the correct bin for cards 3 and 4; every other bin is correct for exactly one card.

Learner Activity:

  1. The learner reads the card at the top of the deck and places it in one of the 7 bins.
  2. The sim immediately marks the placement correct or incorrect and shows the "Why" text. An incorrect card then moves to its correct bin, marked as missed.
  3. The next card appears. The learner continues until all 8 cards are placed.
  4. A "Try again" control reshuffles the deck for a fresh, unscored-for-mastery practice round.

Feedback: 8 cards, shuffled order, one scored attempt per card. Correct: "Correct. " followed by the Why text. Incorrect: "Not quite. This is a . " followed by the Why text. A running count "Correct: n of 8" is shown, and at the end the message is either "Mastery: 7 or more of 8" or "Review the sections on the devices you missed, then try again."

Starting State: The 7 empty bins and the first card. The prompt reads "Which device fits this situation?"

Chapter Anchors: Blast gate maximum temperature 250°F; blast gate bolt pattern 125# ASA pipe flange; nested inlet vanes for clean airstreams up to 600°F; slide gate dampers on cast aluminum pressure blowers.

Inlet Venturis

An inlet venturi is a smooth, bell-shaped entry piece mounted on an open fan inlet, or on the free end of an inlet silencer, so that unducted air enters with as little turbulence and loss as possible. FanPedia pictures it beside the inlet funnels (p. 89), and it shares their aliases: inlet cone, funnel and inlet bell. The practical distinction is placement. An inlet funnel is part of the fan, guiding air into the impeller; an inlet venturi is fitted where air enters the system from the room. FanPedia's inlet silencer description, for example, offers the far end of the silencer with an inlet venturi, an inlet flange or an inlet pipe assembly (p. 188). A venturi is the right answer when a blower or silencer draws straight from open air and the buyer wants the entry to perform like a clean, ducted inlet.

Inlet Box Styles and the Horn

An inlet box turns the air 90 degrees into the fan when there is no room for a straight run of duct, and it is designed to minimize the system effect of that turn (FanPedia p. 187; system effect is covered in Chapter 25). Chapter 18 separated integral boxes from detached ones. FanPedia lists four styles in total: integral with horn, integral without horn, detached bolt-on, and detached free-standing (p. 141).

A bolt-on inlet box is a detached box bolted directly to the inlet flange of the fan (FanPedia pp. 142, 187). It has a rectangular inlet flange that connects to the customer's ductwork, a round outlet flange that connects to the fan inlet flange, and a mounting structure of a single base angle, gussets and a reinforcement plate. It is available with a straight or a flared connection, and FanPedia names it TCF's preferred inlet box design.

A free-standing inlet box is the same concept, except that it is mounted separately from the fan and fully supported at the floor (p. 187). It connects to the fan in one of two ways, and one must be selected: a round outlet flange for a bolted connection, or an outlet collar that joins the fan inlet collar with a rubber sleeve and clamps for a slip connection (p. 142). Its mounting structure is a base plate (foot), gussets and a reinforcement plate. A free-standing box makes sense when the box is too large to hang on the fan, or when the fan and box sit on different supports.

An inlet box horn is an extension on an integral inlet box that carries the inlet connection out past the fan. FanPedia's note (p. 141) is precise: horns are used when the inlet and discharge airflows would intersect, and the horn lets ductwork be connected without interference. Discharge position and inlet box position together decide whether a horn is needed, which is one more reason both are read from the drive side (Chapter 12).

The table summarizes the four styles.

Inlet box style Supported by Connection to fan Use it when
Integral, without horn The fan Part of the housing Standard attached box; no duct interference
Integral, with horn The fan Part of the housing Inlet and discharge airflows would intersect
Detached, bolt-on Base angle to mounting surface Bolted to the fan inlet flange Default detached choice (TCF's preferred design)
Detached, free-standing Base plate, fully at the floor Bolted flange or slip collar Box supported separately from the fan

Diagram: Inlet Box Styles

Run Inlet Box Styles Fullscreen

Inlet Box Styles

sim-id: ch19-inlet-box-styles-overlay
Library: html + FP.Overlay
Status: built
Bloom Level: Remember
Learning Objective: The learner will identify the integral inlet box without horn, the integral inlet box with horn, the bolt-on inlet box and the free-standing inlet box on FanPedia's drawings, given a description of each.

Content: 4 numbered zones: Integral inlet box without horn, Integral inlet box with horn, Bolt-on inlet box, Free-standing inlet box

Provenance: FanPedia pages 141-142, "Inlet Boxes: Overview and Styles, integral inlet box without and with horn (p. 141) and detached bolt-on and free-standing inlet boxes (p. 142)", with the printed labels removed. Drawing: FanPedia, Twin City Fan, pp. 141-142.

Connecting the Fan to the Duct

Every fan ends at two joints, inlet and outlet, and the joint type matters to the installer as much as any rating. Four connection types and one standard appear on Twin City Fan orders.

A bolted flange connection joins two mating flanges with bolts through matching hole patterns, usually with a gasket between them. It is rigid and airtight, and it is the normal joint between a fan's inlet or outlet flange and a companion flange on the ductwork. On a free-standing inlet box, the bolted connection uses the round outlet flange, and the slip connection uses an outlet collar instead; each part comes only with its own connection (FanPedia p. 142).

A slip connection joins a collar to a mating collar or pipe by sliding one over or into the other and sealing the joint, typically with a rubber sleeve held by clamps. FanPedia shows it on free-standing inlet box outlet collars (p. 142) and on welded square-to-round transitions with a slip connection on the outlet (p. 67). Because the sleeve can flex, a slip connection tolerates small misalignment and movement that a bolted joint cannot.

A flexible connector, also called a flex connector or expansion joint, is a short section of flexible material that joins the fan's inlet or outlet to the ductwork (FanPedia pp. 126, 187). It reduces vibration transmission to and from the connecting ductwork and allows for some misalignment. Flex connectors are required on all isolated fans, are available round or rectangular, can be supplied by TCF or by the customer, and are shipped loose for field mounting. FanPedia also requires a flex connector, in the form of a slip connection, between a fan and a detached inlet box mounted on different planes, such as a fan on an isolation base with its inlet box on grade (p. 143).

Isolated Fan, Rigid Duct

Breeze cautioning Watch out for an order with spring isolators and hard-bolted duct at both ends. The duct ties the fan back to the structure and defeats the isolators, and it can load the fan housing as the springs move. Add flexible connectors at the inlet and outlet; FanPedia lists them as required on all isolated fans.

A tube adapter and sleeve (FanPedia's full name is tube adapter and rubber sleeve with clamps) is a ready-made flexible outlet connection for pressure blowers (pp. 127, 194). It consists of a 4-inch-long metal collar and flange that bolts to the blower discharge, plus a 6-inch-long, 2-ply molded rubber slip-type connector with two hose clamps that joins the adapter to the pipe line. The sleeve helps isolate vibration and noise from the rest of the system. The connector is rated for pressures up to 5 psi and 180°F. It is also called a flanged adapter with rubber sleeve and clamps, a flange with boot, a mounting flange with boot, or simply a flex connector.

The ASA pipe flange bolt pattern is the bolt-hole layout of a standard 125-pound-class pipe flange, written "125# ASA" in FanPedia. ASA is the American Standards Association, the predecessor of today's ANSI, and Class 125 is a common pressure class for cast iron pipe flanges, now published in ASME B16.1. A fan component with a 125# ASA bolt pattern bolts directly to an ordinary pipe flange, valve or fitting of the same nominal size. FanPedia states this for the blast gate and for the tube adapter (pp. 125, 180, 194).

Check the Pipe Size, Not Just the Pattern

Breeze with a tip Here's a quick sanity check: when a customer says "it bolts to our pipe," ask for the nominal pipe size and the flange class. A 125# ASA pattern matches only a flange of the same nominal size and class, so both numbers belong on the order.

Before the practice activity, here is how these choices line up for the most common situations.

Situation Usual connection
Fan on isolators, joining duct Flexible connector at inlet and outlet
Free-standing inlet box and fan on different planes Flex connector as a slip connection
Rigid fan, companion flange on the duct Bolted flange connection
Pressure blower into a pipe line, within 5 psi and 180°F Tube adapter and rubber sleeve
Blower outlet to a standard pipe flange or valve 125# ASA bolt pattern, bolted

Diagram: Fan-to-Duct Connection Chooser

Run Fan-to-Duct Connection Chooser Fullscreen

Fan-to-Duct Connection Chooser

Type: microsim sim-id: ch19-fan-duct-connection-chooser
Library: p5.js
Status: Specified
Bloom Level: Apply
Bloom Verb: use
Learning Objective: The learner will use the support, alignment, temperature and pressure facts in a job description to choose the inlet box style or fan-to-duct connection that fits it, with at least 7 of 8 correct on the first attempt.

Prerequisites: bolted flange connection, slip connection, flexible connector, tube adapter and sleeve, 125# ASA pipe flange bolt pattern, bolt-on inlet box, free-standing inlet box and inlet box horn (all defined in the sections above).

Evidence of Mastery: For each of 8 job descriptions, the learner selects one of the 7 options and presses "Submit". An answer is correct when it is in the Accepted answers column. Mastery is 7 of 8 correct on the first attempt. Opening the option definitions is exploration, not evidence.

Misconceptions: (1) A rubber sleeve connector can be used at any temperature. (2) A bolted joint is fine on a spring-isolated fan. (3) Any detached inlet box is supported by the fan. (4) A horn is a sound-control device.

Instructional Rationale: Applying the rules requires the learner to find the deciding fact (isolation, separate support, a temperature limit, intersecting airflows) in a description and act on it. Item 4 changes only the temperature from item 3, so the learner must use the 180°F limit rather than pattern-match the word "blower".

Content:

Options (7), each with a definition the learner can open: Bolted flange connection; Slip connection; Flexible connector; Tube adapter and rubber sleeve; Bolt-on inlet box; Free-standing inlet box; Inlet box horn.

# Job description shown to the learner Accepted answers Why (shown as feedback)
1 A centrifugal fan sits on a spring isolation base. Its outlet joins rectangular ductwork. Flexible connector Flex connectors are required on all isolated fans to block vibration and allow misalignment.
2 A free-standing inlet box sits on grade; the fan is on an isolation base, so they are on different planes. Slip connection; Flexible connector FanPedia requires a flex connector, as a slip connection, between a fan and inlet box on different planes.
3 A pressure blower discharges into a pipe line at 3 psi and 150°F. The plant wants vibration and noise kept out of the piping. Tube adapter and rubber sleeve The rubber sleeve isolates vibration and noise and is rated up to 5 psi and 180°F, so 3 psi and 150°F are within it.
4 The same blower and pipe line, but the airstream is 220°F. The pipe flange is a 125# ASA flange of the same size. Bolted flange connection 220°F exceeds the sleeve's 180°F rating, so bolt the blower to the matching 125# ASA pipe flange instead.
5 Ductwork must turn 90 degrees into the fan in a tight space, and the box should bolt directly to the fan's inlet flange. Bolt-on inlet box The bolt-on box bolts to the fan inlet flange and is TCF's preferred inlet box design.
6 The inlet box must be fully supported at the floor, separate from the fan. Free-standing inlet box A free-standing box is mounted separately and fully supported at the floor.
7 An integral inlet box is specified, but the inlet duct would cross the path of the fan's discharge airflow. Inlet box horn Horns are used when inlet and discharge airflows would intersect, so the duct connects without interference.
8 A free-standing inlet box and its fan share one rigid base on the same plane. The box outlet must join the fan's inlet flange. Bolted flange connection The free-standing box's round outlet flange goes with the bolted connection; the outlet collar goes with the slip connection.

Provenance: FanPedia pp. 67, 126, 127, 131, 132, 141, 142, 143, 187 and 194 and the chapter section "Connecting the Fan to the Duct". Job descriptions are illustrative scenarios.

Rules: Ratings used for judging: tube adapter sleeve acceptable when pressure <= 5 psi and temperature <= 180°F; otherwise not acceptable. An answer is correct when it is any entry in the Accepted answers column for that item. Each item is scored on its first submission only.

Learner Activity:

  1. The learner reads job description 1 and may open any option's definition.
  2. The learner selects one option and presses "Submit". The sim marks the answer and shows the Why text; the item is then locked.
  3. The learner presses "Next" and repeats for items 2 through 8, in the fixed order of the Content table, so that items 3 and 4 appear back to back.
  4. After item 8, a summary lists each item with the learner's answer and the accepted answers, and a "Start over" control clears all answers.

Feedback: 8 items, fixed order, one scored attempt each. Correct: "Correct. " followed by the Why text. Incorrect: "Not this one. " followed by the Why text and the accepted answer. For item 4, if the learner chooses the tube adapter, the incorrect message adds "Check the temperature against the sleeve's 180°F rating." A running count "Correct: n of 8" is shown, and the summary shows "Mastery: 7 or more of 8" or "Review the sections on the items you missed."

Starting State: Job description 1 with no option selected. The prompt reads "How should this fan connect?"

Chapter Anchors: Tube adapter sleeve rated to 5 psi and 180°F; tube adapter collar 4 inches long and sleeve 6 inches long with two hose clamps; flex connectors required on all isolated fans; bolt-on inlet box is TCF's preferred design; horns used when inlet and discharge airflows would intersect.

Key Takeaways

  • Ceiling type and wall type gravity dampers share one description (parallel blade, end-pivoted, open on fan start, close by gravity, block backflow and weather); they differ in mounting plane.
  • Flat blade (Type 1) and airfoil blade (Type 2) dampers are both offered for outlet dampers; the parallel blade inlet box damper is Type 2 only.
  • Blade flutter comes from airflow holding blades partly open at low flow; a damper actuator powers the blades to position and prevents it.
  • Damper throttling adds resistance and moves the operating point left on the fan curve; it is inexpensive but saves less horsepower than other methods.
  • A blast gate is a wafer butterfly valve at the outlet flange for flow control to full shutoff, rated to 250°F, with a 125# ASA bolt pattern; a slide gate damper gives manual adjustment on cast aluminum pressure blowers.
  • On lab exhaust fans, isolation dampers seal off idle fans and bypass dampers admit outside air to keep fan flow and plume constant.
  • Pre-spin turns incoming air in the direction of rotation, reducing the work the impeller does; nested inlet vanes deliver it from within the inlet funnel for clean air up to 600°F.
  • An inlet venturi gives an open inlet or silencer end a smooth, low-loss entry.
  • Inlet boxes come integral (with or without a horn), detached bolt-on (TCF's preferred design) and detached free-standing (floor-supported, bolted or slip connection).
  • Bolted flanges are rigid; slip connections and flexible connectors tolerate movement, and flex connectors are required on all isolated fans. The tube adapter and rubber sleeve suits pressure blower pipe lines up to 5 psi and 180°F.

Connections Covered

Breeze celebrating You can now specify how a fan joins its ductwork and its controls, from the gravity damper on the opening to the flange pattern on a blower outlet. That is the detail that turns a fan selection into a fan that installs.