Anatomy of a Fan Duty Statement¶
Run the Anatomy of a Fan Duty Statement MicroSim Fullscreen
About This MicroSim¶
A duty statement is the line on a schedule or specification that tells you what a fan must do. This infographic shows the one built from Chapter 1's worked examples:
12,000 CFM at 3.0 in. wg static pressure, 1,173 RPM, 7.9 BHP, at 0.075 lb/ft³ (70°F, sea level), clean air.
Its six parts are marked as clickable segments, each with its quantity name underneath:
| # | Segment | Quantity name | What it tells you |
|---|---|---|---|
| 1 | 12,000 CFM | Airflow volume | Cubic feet of air per minute, measured at the fan inlet conditions. |
| 2 | 3.0 in. wg static pressure | Static pressure | The system's resistance at this airflow, which the fan must overcome. |
| 3 | 1,173 RPM | Fan speed | Impeller revolutions per minute; here set by a 6 in motor sheave and a 9 in fan sheave on a 1,760 RPM motor. |
| 4 | 7.9 BHP | Brake horsepower | Power required at the fan shaft; a 10 hp motor would run at 79 percent load. It is not the motor size. |
| 5 | 0.075 lb/ft³ (70°F, sea level) | Air density | The density the rating assumes; here standard air. Hot air or a high site changes pressure and power. |
| 6 | clean air | Airstream condition | What the air carries; contaminated airstreams change the impeller, arrangement and construction. |
In Explore mode, clicking a segment opens its callout. A ✓ badge marks each part you have opened ("Visited n of 6").
In Quiz mode the names are hidden. The sim highlights one segment at a time, in an order shuffled once per session, and you choose its name from the six quantity names. Each segment has one scored attempt. A correct choice shows "✓ Correct:
The duty statement is illustrative, not a catalog selection, and the infographic says so.
How to Use¶
- In Explore mode, click each part of the rating line (or Tab to it and press Enter) and read its callout.
- When you know all six, press Quiz.
- For each highlighted part, choose its name (or press 1 to 6). Read the feedback, then press Next prompt.
- Read the summary. Press Back to explore to review the parts, or Start over for a new quiz.
Keyboard: Tab moves between the parts and the buttons; Enter or Space opens a part; in the quiz, keys 1 to 6 pick a name, and Enter on Next prompt goes on.
Data label: "Illustrative duty statement, not a catalog selection · Values from the Chapter 1 worked examples", shown under the rating line.
Iframe Embed Code¶
You can add this MicroSim to any web page by adding this to your HTML:
<iframe src="https://moroshek.github.io/FanTASTIC-textbook/sims/ch01-fan-duty-statement/main.html"
height="722px"
width="100%"
scrolling="no"></iframe>
Lesson Plan¶
Learning Objective¶
The learner will identify each of the six parts of a fan duty statement by its quantity and unit, with at least 5 of 6 correct on the first attempt (Bloom: Remember, verb: identify).
Audience¶
Adult professional development: new application engineers, sales staff, representatives and facilities staff.
Duration¶
5-10 minutes
Prerequisites¶
- Airflow volume and cubic feet per minute
- Static pressure and inches of water gauge
- Fan speed and RPM
- Brake horsepower
- Air density and standard air
- Airstream
All are defined earlier in Chapter 1.
Activities¶
- Explore (3 min): Open all six callouts. For each, say which unit tells you what the quantity is.
- Quiz (3 min): Name the six highlighted parts without the labels.
- Discussion (2 min): A customer's schedule gives only "12,000 CFM at 3.0 in. wg". What two parts are missing, and why can the line not be checked against a catalog without them?
Common Misconceptions Addressed¶
- BHP is the motor nameplate size: the brake horsepower callout says it is the power at the fan shaft, with a 10 hp motor running at 79 percent load.
- Static pressure is a property of the fan alone: its callout calls it the system's resistance at this airflow.
- The density can be left off because every catalog uses standard air: its callout says hot air or a high site changes pressure and power.
Assessment¶
- First-attempt score shown as "Correct on first attempt: n of 6"; mastery is 5 of 6 on the first attempt. The summary shows "Mastery reached (5 of 6 needed)." or what is still needed.
- Explore mode is not evidence of mastery. Follow up: rewrite the line for 250°F air. Which parts change, and which stay the same?
References¶
- Chapter 1: Air, Pressure and the Fan - "Putting It Together: What a Fan Delivers" and the worked examples "From Duty Point to Motor" and "Setting a Belt-Driven Fan's Speed".
- FanPedia online, Twin City Fan - The fan and blower encyclopedia this textbook is built from.
- Chapter 26: Reading Catalogs and Performance Tables - Where to find this line in a performance table.