About This MicroSim

Catalog ratings assume standard air (0.075 lb/ft³ at 70°F and sea level). This calculator practices the density corrections from the section "Density Corrections" in Chapter 10:

  • Temperature factor: Kt = 530 ÷ (T + 460), with T in °F
  • Altitude factor: Ka = (1 − 6.875 × 10⁻⁶ × h)^5.2559, with h in feet
  • Combined factor: Kd = Kt × Ka
  • Standard-air pressure for catalog selection = actual pressure ÷ Kd
  • Actual BHP = catalog BHP × Kd

The sim starts with three challenge jobs, in this fixed order (illustrative values; job 3 is the chapter's worked example "A Hot Fan at Altitude"):

# Job Asked Model answer
1 200°F air at sea level (0 ft) Combined factor 0.803
2 70°F air at 5,000 ft Combined factor 0.832
3 200°F air at 5,000 ft, 3.0 in. wg actual static pressure, 10,000 CFM Combined factor, then standard-air pressure 0.668, then 4.49 in. wg

A factor is correct within ±0.01 of the model value and a pressure within ±0.05 in. wg. Every answer gets two attempts; after the second wrong attempt the model value is shown and the answer counts as missed. Job 3 has two parts: the pressure question appears only after the factor is checked, and the job counts as correct only when both parts are. Two common slips get an extra line: a job-1 factor near 70 ÷ 200 = 0.35 ("Add 460 to each temperature first.") and a job-3 pressure near 3.0 × 0.668 = 2.00 ("That multiplies by the factor; to enter a standard-air catalog, divide by it."). After each answer the sim shows the model value and the one-line calculation, and the factor chain Kt × Ka = Kd on the right fills in.

Mastery is 3 of 3 jobs fully correct on the first attempt. After job 3, Explore mode unlocks four sliders: air temperature (0 to 800°F), site elevation (0 to 10,000 ft), actual static pressure (0.5 to 15.0 in. wg) and catalog BHP at the standard-air point (1.0 to 200.0 BHP). The three factors, the standard-air pressure and the actual BHP update at once. Explore mode is never scored.

How to Use

  1. Read job 1, type the combined factor in Your answer and press Check (or Enter).
  2. A correct answer reads "✓ Correct: model value." in a solid green box. A wrong one reads "✗ Not quite." with the calculation hint in a dashed red box; use the second attempt.
  3. Press Next challenge (or Enter) for job 2, then job 3: type the factor, press Next: part 2, and type the standard-air pressure. "Challenges correct: n of 3" keeps the running score.
  4. After job 3, press Start exploring. Set 800°F at sea level and see the combined factor fall to 0.421, so the catalog pressure is more than twice the job pressure. Set 200°F, 5,000 ft, 3.0 in. wg and 11.0 BHP to see the chapter's dryer example: 4.49 in. wg in, 7.35 BHP out. Start over clears the score and returns to job 1.

Keyboard: Enter checks the answer, and Enter again goes to the next part or job. Tab reaches the answer box, every button and the four sliders; the arrow keys move a focused slider.

Data label: "Illustrative values · standard air 0.075 lb/ft³ at 70°F, sea level", at the bottom left of the drawing.

Iframe Embed Code

You can add this MicroSim to any web page by adding this to your HTML:

<iframe src="https://moroshek.github.io/FanTASTIC-textbook/sims/ch10-density-correction-calculator/main.html"
        height="642px"
        width="100%"
        scrolling="no"></iframe>

Lesson Plan

Learning Objective

The learner will calculate the combined density correction factor for a stated air temperature and site elevation, and use it to convert an actual static pressure to the standard-air pressure used for catalog selection, to within ±0.01 on the factor and ±0.05 in. wg on the pressure (Bloom: Apply, verb: calculate).

Audience

Adult professional development: new application engineers, sales staff, representatives and facilities staff who have read the section "Density Corrections" in Chapter 10.

Duration

10-15 minutes

Prerequisites

  • Standard air and the density correction factor
  • Temperature correction and degrees Rankine (°F + 460)
  • Altitude correction

Activities

  1. Challenges (5-8 min): Work each job with a calculator before pressing Check. Write Kt and Ka separately, then multiply.
  2. Review (2 min): For job 3, say aloud which way each value goes: pressure into the catalog is divided by Kd; horsepower out of the catalog is multiplied by Kd.
  3. Explore (3-5 min): Find the temperature at which the catalog pressure is half again the job pressure at sea level (Kd about 0.667, near 335°F), then add elevation and watch it grow.

Common Misconceptions Addressed

  • The fan moves less CFM in hot or thin air at the same speed: the sim repeats that airflow volume is the same at any density for a fan at fixed speed.
  • The actual pressure is multiplied by the factor to get the catalog pressure: a job-3 answer near 2.00 in. wg gets the "divide by it" correction.
  • Temperature in °F can be used directly in the ratio: a job-1 answer near 0.35 gets the "add 460" correction.

Assessment

  • The running line "Challenges correct: n of 3" counts jobs solved on either attempt. At the end the sim shows "First-attempt score: n of 3" and the mastery line; mastery is 3 of 3 jobs fully correct on the first attempt.
  • Moving the sliders in Explore mode is not evidence of mastery. Ask the learner why a hot fan needs a cold-start motor check.

References

  1. Density of air - Wikipedia article on how air density varies with temperature and pressure.
  2. Barometric formula - Wikipedia article on the standard-atmosphere pressure change with altitude behind the altitude factor.
  3. FanPedia: The Fan & Blower Encyclopedia - Twin City Fan's reference on fan ratings at standard air and corrections for temperature and altitude.